Process Load Errors
I noticed a negative comments about the process loads, so instead of just complaining I figured I would do something, because as a Professional Engineer I should be able to solve this problem or at least identify what it is, I mean I actually know psychometrics.
It’s pretty obvious that if the total load is over 1 million BTUs the app errors out, it be nice if the programmers fix it, but any engineer that can’t figure that out should you should ask yourself should you really be designing air-conditioning systems, just do the calculation with half the CFM and multiply by two problems solved.
It’s pretty obvious that if the total load is over 1 million BTUs the app errors out, it be nice if the programmers fix it, but any engineer that can’t figure that out should you should ask yourself should you really be designing air-conditioning systems, just do the calculation with half the CFM and multiply by two problems solved.
Show more
Not bad
not bad.
Process calculations are incorrect
Obvious errors in calculating process loads with new version of App
Something very wrong in process calc
20,000 cfm from 95/77 to 55/54.5 is most certainly NOT 9 Tons. Something is very wrong here.